TEL 262-654-3833 | Hours 8AM-5PM Central Standard Time M - F
Select Page

TTP Electric Control Temperature 55927 (0-194F)

Call for Price

TTP Electric Control Temperature 55927 CE temperature range (0 – 194F). Immersion thermostat, measuring temperature with a liquid filled sensing element, Capillary Length: 39″, Max. 257F copper bulb.

Description

TTP Electric Control Temperature 55927 CE (0 – 194F)

Immersion thermostat, measuring temperature with a liquid filled sensing element. SPDT contacts, complete with waterproof protection pocket. Used to measure temperature on the primary heating pipe circuit, it is particularly suitable for automatic adjustment pumps.

Features

  • Contacts rating: 10(2,5)A/250V~
  • Contacts: switching or closing contact for temperature increase
  • Maximum head temperature: 176°F (80°C)
  • Maximum bulb temperature: 257°F (125°C)
  • Temperature rate of change: 1° K/min
  • Protection degree: IP40

Specifications

  • Part Number: 55927
  • Temperature Range: 0°/194°F (0°/90°C)
  • Differential: t = 4 ± 1K
  • Maximum Bulb Temperature: 266°F (130°C)
  • Capillary Length: 39″ (1000 mm)
  • Protection Pocket 1/2″ NPT: N/A
  • Copper Bulb: Ø .26×3.7″ (6.5 x 95 mm)

 

55925, 55926, 55927 Specifications Sheet

Additional information

Weight 2 lbs
Dimensions 12 × 8 × 5 in
Manufacturer Part Number

Reviews

There are no reviews yet.

Be the first to review “TTP Electric Control Temperature 55927 (0-194F)”

Your email address will not be published. Required fields are marked *

Share This